Rinnai Error Code 2
No Burner Operation During Freeze Protection Mode
Rinnai Error Code 3
Power Interruption During Bath Fill (Water will not flow when power returns).
Check this first
- Turn off all hot water taps. Press ON/OFF twice.
Rinnai Error Code 5
By-Pass Flow Control
Leave to a technician
- Measure resistance values of the by-pass flow control.
- Replace By-Pass flow control device.
Rinnai Error Code 10
Air Supply or Exhaust Blockage
Check this first
- Check that nothing is blocking the flue inlet or exhaust.
- Check all vent components for proper connections.
Leave to a technician
- Ensure approved venting materials are being used.
- Ensure vent length is within limits.
- Verify dip switches are set properly.
- Check fan for blockage.
Rinnai Error Code 11
No Ignition (Heating Not Turning On)
Check this first
- Check that the gas is turned on at the water heater, gas meter, or cylinder.
- If the system is propane, make sure that gas is in the tank.
- Ensure appliance is properly grounded.
Leave to a technician
- Ensure gas type and pressure is correct.
- Ensure gas line, meter, and/or regulator is sized properly.
- Bleed all air from gas lines.
- Verify dip switches are set properly.
- Disconnect EZConnect™ or MSA controls to isolate the problem.
- Ensure igniter is operational.
- Check igniter wiring harness for damage.
- Check gas solenoid valves for open or short circuits.
- Remove burner cover and ensure all burners are properly seated.
- Remove burner plate and inspect burner surface for condensation or debris.
- Check the ground wire for the PC board.
Rinnai Error Code 12
Flame Failure - No Flame
Check this first
- Check that the gas is turned on at the water heater, gas meter, or cylinder.
- Check for obstructions in the flue outlet.
- If the system is propane, make sure that gas is in the tank.
Leave to a technician
- Ensure gas line, meter, and/or regulator is sized properly.
- Ensure gas type and pressure is correct.
- Bleed all air from gas lines.
- Ensure proper venting material was installed.
- Ensure condensation collar was installed properly.
- Ensure vent length is within limits.
- Verify dip switches are set properly.
- Ensure appliance is properly grounded.
- Disconnect keypad.
- Disconnect EZConnect™ or MSA controls to isolate the problem.
- Check power supply for loose connections.
- Check power supply for proper voltage and voltage drops.
- Ensure flame rod wire is connected.
- Check flame rod for carbon build-up.
- Disconnect and reconnect all wiring harnesses on unit and PC board.
- Check for DC shorts at components.
- Check gas solenoid valves for open or short circuits.
- Remove burner plate and inspect burner surface for condensation or debris.
Rinnai Error Code 14
Thermal Fuse has Activated
Check this first
- Check for restrictions in air flow around unit and vent terminal.
Leave to a technician
- Ensure SW 5 in DIPSW 2 is in the off position.
- Check gas type of unit and ensure it matches gas type being used.
- Check for low water flow in a circulating system causing short-cycling.
- Ensure dip switches are set to the proper position.
- Check for foreign materials in combustion chamber and/or exhaust piping.
- Check heat exchanger for cracks and/or separations.
- Check heat exchanger surface for hot spots which indicate blockage due to scale build-up. Refer to instructions in manual for flushing heat exchanger.
- Hard water must be treated to prevent scale build up or damage to the heat exchanger.
- Measure resistance of safety circuit.
- Ensure high fire and low fire manifold pressure is correct.
- Check for improper conversion of product.
Rinnai Error Code 15
Venturi Control
Leave to a technician
- Ensure the Venturi motor is operating correctly.
- Replace gas valve assembly.
- Clear diagnostic code by resetting the main power supply to the water heater.
Rinnai Error Code 16
Over Temperature Warning (Safety Shutdown Because Unit is Too Hot)
Check this first
- Check for restrictions in air flow around unit and vent terminal.
- Confirm fan motor is functioning correctly.
Leave to a technician
- Check for low water flow in a circulating system causing short-cycling.
- Check for foreign materials in combustion chamber and/or exhaust piping.
- Check for blockage in the heat exchanger.
- Replace the gas valve assembly.
Rinnai Error Code 17
Venturi Blockage
Leave to a technician
- Ensure Venturi isn’t blocked.
- Call Rinnai technical department.
Rinnai Error Code 19
Electrical Grounding
Leave to a technician
- Check all components for electrical short.
Rinnai Error Code 21
Data Transfer Error
Leave to a technician
- If the PCB has been replaced, ensure the data transfer process has been completed.
Rinnai Error Code 25
Condensate Pump (Accessory) Condense Trap is Full
Leave to a technician
- Confirm wire connections and harness are good.
- Ensure condensate reservoir is empty and condensate pump is operating.
Rinnai Error Code 31
Burner Sensor Error
Check this first
- Measure resistance of sensor.
- Replace sensor.
Rinnai Error Code 32
Outgoing Water Temperature Sensor Fault
Leave to a technician
- Check sensor wiring for damage.
- Measure resistance of sensor.
- Clean sensor of scale build-up.
- Replace sensor.
Rinnai Error Code 33
Heat Exchanger Outgoing Temperature Sensor Fault
Leave to a technician
- Check sensor wiring for damage.
- Measure resistance of sensor.
- Clean sensor of scale build-up.
- Replace sensor.
Rinnai Error Code 34
No Burner Operation During Freeze Protection Mode
Leave to a technician
- Check for restrictions in air flow around unit and vent terminal.
- Check sensor wiring for damage.
- Measure resistance of sensor.
- Clean sensor of scale build-up.
- Ensure fan blade is tight on motor shaft and is in good condition.
- Replace sensor.
Rinnai Error Code 38
Exhaust Thermistor CO Sensor
Leave to a technician
- Check sensor wiring for damage.
- Measure resistance of sensor.
- Clean sensor of scale build-up.
- Replace sensor.
Rinnai Error Code 41
Outside Temperature Thermistor Freeze Protection Sensor
Leave to a technician
- Check sensor wiring for damage.
- Measure resistance of sensor.
- Clean sensor of scale build-up.
- Replace sensor.
Rinnai Error Code 51
Inlet Water Temperature Thermistor (Sensor)
Leave to a technician
- Check sensor wiring for damage.
- Measure resistance of sensor.
- Clean sensor of scale build-up.
- Replace sensor.
Rinnai Error Code 52
Inlet Water Temperature Thermistor (Sensor)
Leave to a technician
- Check modulating gas solenoid valve wiring harness for loose or damaged terminals.
- Measure resistance of valve coil.
Rinnai Error Code 54
High Exhaust Gas Temperature
Leave to a technician
- Ensure Heat Exchanger fins are clean and not blocked.
- Confirm inlet water temperature is not too high.
- Clear diagnostic code by resetting the main power supply to the water heater.
Rinnai Error Code 57
Burner Overheat Bi-Metal Switch
Rinnai Error Code 58
Secondary Heat Exchanger Sensor
Leave to a technician
- There is scale build up in the secondary heat exchanger and it needs to be flushed to prevent damage. Refer to the flushing instructions in the manual. Hard water must be treated to prevent scale build up or damage to the heat exchanger.
Rinnai Error Code 61
Combustion Fan Motor Failure
Leave to a technician
- Ensure fan will turn freely.
- Check wiring harness to motor for damaged and/or loose connections.
- Measure resistance of motor winding.
Rinnai Error Code 63
Recirculation Low Flow Circulation Flow Rate dropped below 1.3 GPM
Leave to a technician
- Ensure bypass plug is removed and bypass filter is installed. (Crossover Mode)
- Ensure both the inlet water filter and bypass filter are clean and free of debris.
- Ensure Parameter setting are correctly set for recirculation mode.
- Ensure Pump supply voltage.
- Ensure air is removed from the recirculation line.
Rinnai Error Code 65
Water Flow Control Fault
Leave to a technician
- The water flow control valve has failed to close during the bath fill function. Immediately turn off the water and discontinue the bath fill function. Contact a state qualified or licensed contractor to service the appliance.
Rinnai Error Code 70
PC Board
Leave to a technician
- Check PC board DIP switches for correct position.
- Check the connection harness at the connection on the PC board.
- Replace PC board.
Rinnai Error Code 71
Solenoid Valve Circuit Fault
Leave to a technician
- Replace PC board.
Rinnai Error Code 72
Flame Sensing Device Fault
Leave to a technician
- Ensure flame rod is touching flame when unit fires.
- Check all wiring to flame rod for damage.
- Remove flame rod and check for carbon build-up; clean with sand paper.
- Check inside burner chamber for any foreign material blocking flame at flame rod.
- Measure micro amp output of sensor circuit with flame present.
- Replace flame rod.
Rinnai Error Code 73
Flame Sensing Device Fault
Leave to a technician
- Check sensor wiring and PC board for damage.
- Replace sensor.
Rinnai Error Code 79
Flame Sensing Device Fault
Leave to a technician
- Water has been detected at the bottom of the unit. Turn off water supply.
- Check all plumbing internally for leakage.
Rinnai Error Code LC
Scale Build-up in Heat Exchanger (when checking maintenance code history, “00” is substituted for “LC”)
Check this first
- NOTE: The LC code is the only error code that will allow the unit to keep running. The display will alternate between the LC code and the temperature setting. The controller will continue to beep. The LC code will reset if power is turned off and then on.
- Flush heat exchanger. Refer to instructions in manual.
- Replace heat exchanger.
- LC0-LC9 indicates that there is scale build up in the heat exchanger and that the heat exchanger needs to be flushed to prevent damage. Refer to the flushing instructions in the manual. Hard water must be treated to prevent scale build up or damage to the heat exchanger.
- To operate the water heater temporarily until the heat exchanger can be flushed, push the On/Off button on the temperature controller 5 times. Repeated LC codes will eventually lockout the water heater.
Leave to a technician
- Water has been detected at the bottom of the unit. Turn off water supply.
- Check all plumbing internally for leakage.
Rinnai Error Code SS
(SS) Service Soon (Flush Heat Exchanger)
Check this first
- SS is a time-based service indicator set during installation.
- See section “3.12 Parameter Settings” for additional details on setting and changing the SS indicator.
- SS indicates that it is time for service. The heat exchanger should be flushed to prevent damage (refer to section Flushing the Heat Exchanger for more information).
- Hard water must be treated to prevent scale build-up or damage to the heat exchanger.
- To reset the SS code, push the On/Off button on the temperature controller 5 times in 5 seconds.
Rinnai Error Code FF
Maintenance Has Been Performed
Check this first
- Indicates a licensed professional performed maintenance or corrected an issue
Rinnai Error Code NO CODE
Maintenance Has Been Performed
Check this first
- Clean inlet water supply filter.
- On new installations ensure hot and cold water lines are not reversed.
- Check for bleed over. Isolate unit from building by turning off cold water line to building.
- Isolate the circulating system if present. Open your pressure relief valve; if water is flowing, there is bleed over in your plumbing.
- Ensure you have at least the minimum flow rate required to fire unit.
- Ensure turbine spins freely.
- Measure the resistance of the water flow control sensor.
- Check for DC shorts at components.
Codes and checks are for general guidance. Gas, venting, and electrical work on a water heater should be done by a licensed plumber.